How should the chiller operate correctly?

This article is mainly to tell everyone if the chiller is operating correctly.
For a running chiller. Under ambient conditions, the load has become constant. At this time, the condensing heat load is also fixed. The temperature difference between the inlet and outlet water is specified to be 5 ° C, and the amount of cooling water must also be a certain value and the flow rate is inversely proportional to the temperature difference between the inlet and outlet water. Therefore, the operation of the chiller. As long as the temperature difference between the inlet and outlet of the cooling water is specified, this flow rate is usually controlled by the pressure drop of the cooling water entering and leaving the condenser. Under standard operating conditions, the pressure drop of the inlet and outlet water of the condenser was set to 68.6 kPa (0, 7 kg/cm:).

In the actual operation of the cooling water system, there are often the following misoperations:

1. Before the chiller is turned on, the inlet valve of the condenser on the unit that does not need to be opened is not closed to cause drowning. A part of the cooling back water flows away from the condenser of the startup group, which reduces the flow of cooling water in the condenser of the running unit, causing the condensing pressure to rise, the operating current of the main engine increases, the cooling capacity of the unit decreases, and the unit will be seriously Stopping the operation wastes electricity, reduces the cooling effect, and easily damages the equipment.

2. Due to the previous misoperation, the condensing pressure of the chiller main engine and the cooling water effluent temperature increase. Cause the operator to make a misjudgment, mistakenly believe that the cooling water is not enough to open the condenser inlet valve and the cooling water pump outlet valve, and some also increase the cooling tower fan, resulting in increased power consumption of the pump and cooling tower fan

3. What's more, blindly add a cooling water pump. Although the addition of the cooling water pump can reduce the cooling water temperature and the condensing pressure, after all, the power of one pump is wasted, so it is wrong to add the wrong cooling water system. The correct operation method is:

1. Before starting the machine, the unit condenser inlet valve will not need to be closed to prevent drowning.

2. Open the inlet and outlet water valve on the condenser of the unit (the general outlet valve is normally open, the inlet valve is opened and closed as needed. The condenser and evaporator are the same). Turn on the corresponding cooling water pump to adjust the inlet and outlet pressure of the condenser. It is reduced to about 68.6 kPa (0.7 kg/cm:) (the pressure drop is based on the principle of overcoming the resistance of the pipeline, and the lower the power saving effect is better).

3. If the pointer of the condenser inlet and outlet water pressure swings too large, it indicates that there is air in the cooling water system, and it is necessary to discharge the air until the pressure gauge indicates normal and continue the next operation.

4 In operation, no matter how many chillers are installed, they are all one cooling water pump to one main unit (the matching is the same).
(End) http://news.chinawj.com.cn How should the chiller operate correctly? Editor: (Hardware Business Network Information Center) http://news.chinawj.com.cn How should the chiller operate correctly?

Different from split Solar Water Heating System, Compact Solar Water Heating System mainly means the system with Vacuum Tubes or heat pipe vacuum tubes inserting into water tanks directly. Compact solar water heating system can be both non-pressurized and Pressurized Solar Water Heating System, it defines solar water heating system only by system structure. 

Compact system mainly means the household solar water heating system.

5

Compact Solar Water Heating System

Solar Heating System,Compact Hot Water System,Compact Water Heating System,Compact Solar Water Heating System

Linuo Ritter International Co.,Ltd , https://www.lnrtsolarenergy.com